| Portable Energy Audit Kit (PLM - TB) | |
|
|
DESCRIPTION |
|
Portable
Energy Audit Kit contains Power line Monitor based on advanced micro controller,
which sample voltage and current signals and compute true RMS voltage
current, Power factor, Power and Energy. Audio kit is provided with three
Clamp on CT's (ratings as per customer) and Four voltage probes. |
|
| APPLICATIONS | |
|
The new AE Audit Kit PLM-TB can be used for Energy Audit purpose for different Industries, Various Manufacturing plants for Maintenance Energy Monitoring System for various commercial complex, hospitals, hotels, for testing and study purpose at various technical institute, for Energy Audit consultants etc. |
| FEATURES | |
|
A portable unit suitable for site application can measure phase wise and overall of all basic Electrical parameters i.e.. Voltage (L-N), Voltage (L-L), Current, Power Factor, Frequency, Apparent Power, Reactive Power, Active Power, Apparent Energy, Reactive Energy, Active Energy, Maximum demand etc. |
|
| | Maximum demand |
| | Export and Import of all Power and Energy parameters |
| | Accuracy 0.5% of full scale reading. |
| | Display of True RMS value. |
| | Backlit LCD Display. |
| | Programmable CTR/PTR. |
| | Advanced Java based Software. |
| | Inbuilt memory of 56KB to store data on site. |
| | Data retention for 10 years. |
| | Inbuilt RS 232 port for communication to PC. |
| | Export historical data to Excel file. |
| | Event recording facility is available. |
| | Suitable to HT and LT systems. |
| | Suitable for single phase and three phase balanced and unbalanced system. |
| | Portable Briefcase, Lockable and rugged design. |
| ELECTRICAL SPECIFICATIONS | ||||||
| TYPE | : 1 Ph / 3 Ph - 2 EL - 3W / 3 Ph - 3 EL - 4W | |||||
| MEASUREMENT | : True R.M.S | |||||
| INPUT VOLTAGE | : 63.5V / 110V / 240V / 440V AC - burden 0.5VA | |||||
| INPUT CURRENT | : 1A/5A - burden 0.5VA | |||||
| OPERATING FREQUENCY | : 45 Hz to 65 Hz | |||||
| OPERATING POWER FACTOR | : 0.1lag - unity - 0.1lead | |||||
| AUXILIARY SUPPLY | : 90VAC - 265VAC, 120VDC TO 300VDC, 5VA | |||||
| ACCURACY | | Power | ± 1% of full scale | | Energy | ± 1% of the reading |
| | Power factor | ± 2° | | Voltage & Current | ± 0.5% of full scale | |
| | Frequency | ± 0.2% of centre frequency | ||||
| RESOLUTION | | Power | 0.2% of full scale | | Voltage & Current | 0.1% of full scale |
| | Power Factor | 0.3° | | Frequency | 0.01% of centre Frequency | |
| DISPLAY | : 16 Char x 2 rows backlit LCD display | |||||
| RESPONSE TIME | : Less than 500ms | |||||
| OVER VOLTAGE | : 1.5 times for 10 seconds | |||||
| OVER CURRENT | : 10 times for 3 seconds | |||||
| INSULATION RESISTANCE | : Greater than 20 M ohms at 500VDC | |||||
| DIELECTRIC TEST | : 2kV RMS for one minute | |||||
| OPERATING TEMPERATURE | : 0 - 55°C | |||||
| STORAGE TEMPERATURE | : -20°C - 70°C | |||||