| Power Factor Controller | |
![]() |
DESCRIPTION |
| It measures system power factor and automatically switches the capacitor banks on/off as required by plant load to maintain desired power factor. Target power factor range is programmable from 0.8 (lag) to unity and dead band setting is provided to avoid over-correction and hunting. Capacitor switching is in sequential method (first in- last out). This method is applicable for equal value capacitor banks, and can be changed to ascending or descending order wherever needed. | |
| Power Factor Controller can be used to eliminate power factor penalty fees from power utility bills by automatically maintaining system power factor within a set range. | |
| FEATURES | |
| • | 4 digit LED display. |
| • | Display of power factor. |
| • | Display of set power factor. |
| • | Display of dead band setting in degrees. |
| • | Auto/Manual operation. |
| • | Power factor setting range 0.8 (lag) to unity. |
| • | Dead band setting range 4 deg. to 14 deg. |
| • | Status of all capacitor banks is displayed by LEDs. |
| • | Status of system power factor w.r.t. setting is displayed on front panel |
| ELECTRICAL SPECIFICATIONS | ||
| • | TYPE | Single phase / 3 phase 1 element. |
| • | OPERATING VOLTAGE | 110V / 240V / 440V AC. 2VA |
| • | OPERATING CURRENT | 1A / 5A.,0.5VA |
| • | RELAY CONTACT RATING | 230V,AC, 5A. |
| • | NO. OF RELAY STAGES | 6 / 8 / 12. |
| • | TIME DELAY FOR RELAY SWITCHING | 5 to 120 seconds |
| • | INSULATION RESISTANCE | Greater than 20 Mohms at 500V DC. |
| • | DIELECTRIC STRENGTH | 2kV RMS for one minute |
| • | OPERATING TEMP. | 0° to 55°C |
| • | STORAGE TEMP. | -20°C to 70°C |
| • | HUMIDITY | Upto 95% RH. |
| MECHANICAL SPECIFICATIONS | ||
| • | MODEL | PFC 144 D |
| • | SIZE | 144 x 144 x 124 mm |
| • | PANEL CUT-OUT | 138 x 138 +1mm |
| • | WEIGHT (Appro.) | 1.8Kg. |
| Ordering information | |
| 1) | Type |
| 2) | Model |
| 3) | Operating voltage |
| 4) | Operating current |
| 5) | No. of relay stages |
| 6) | Time delay for switching |