| H.V.TESTER | |
|
INTRODUCTION |
|
Every
electrical apparatus or machine Is provided with insulation between live
part and earth or between two different sections of live parts. This insulation
is required to be tested at high voltage values recommended by applicable
relevant standards. |
|
|
High
Voltage Tests Sets of higher voltage upto 600kV are also manufactured
against specific requirement. The standard voltages are 10kV, 15kV, 20kV,
25kV, 30kV, 50kV,100kV, 150kV, 200kV & 300kV. The test sets uplo 30kV
are manufactured in Air Cooled design while the sets of 50kV & above
are manufactured in Oil Cooled design. The output of these high voltage
testers is single phase 50/60Hz. The standard H.T. current rating of air-cooled
design as also of oil cooled design upto 150kV is 100mA for 30 minutes.
For voltages ranges above 'AE' make 5kV A.C. (with 2.5kV tap) High Voltage
Breakdown Tester is portable, sturdy & plug in to start type construction
& requires minium table space. It broadly consists of 3 main sections. |
|
| 1) HIGH VOLATGE TRANSFORMER : |
The
High voltage transformer is single phase, single pole type & is of double
wound resin moulded |
| 2) VARIABLE VOLTAGE SOURCE : | |
|
Variable Voltage supply is provided through a Dimmerslat (Variable auto-transformer) havingasuitable rating corresponding to the rating of H.V. Transformer. Dimmerstat Is rated for 230Volts A.C. input & 0-270V output. Limit switch at zero position end of Dimmerstat winding is provided to facilitate the H.T. winding to |
|
| 3) CONTROL CIRCUIT & OTHER FEATURES : | |
| • |
ManuaIly operated control transformer (VariabIe auto-transformer) with zero interlock facility. |
| • |
72mm sq. double range (0-2kV / 0-5kV) moving coil rectifier type voltmeter of class 1.5, provided to read NO LOAD H.T. Voltage. |
| • |
72mm sq. double range (0-100mA) moving coil rectifier type A.C. Milliammeter of class 1.5, provided in the earth end of the H.T. winding to read H.T. Current. |
| • |
Automatic tripping circuit is provided for isolation of supply, in the event of failure of the object under test. Rotary switch with four different settings of 5,10, 50 & 100mA is provided on front panel with LED indication |
| • |
M.C.B. for short circuit protection of H.T. transformer & auto transforme |
| • |
H.T. ON push button, Mains ON & H.T ON LED indication. |
| • |
Range selection switch to select 2.5kV or 5kV range with LED indication. |
| • |
Two spring loaded test prods with 1 metre long cable for safe & easy connection of high voltage to test object, (upto 5kV.) |
| DIMENSIONAL DRAWING : | ||
![]() |
||
| CIRCUIT DIAGRAM : | ||
![]() |
1. | MINITATURE CIRCUIT BREAKER |
| 2. | DIMNERSTAT | |
| 3. | AUXILIARY TRANSFORMER | |
| 4. | VOLTAGE RANGE INDICATOR | |
| 5. | KILO VOLT METER | |
| 6. | RANGE SELECTOR SWITCH | |
| 7. | MAIN 'ON' LED YELLOW | |
| 8. | H.T. ON LED RED | |
| 9. | H.T. ON PUSH BUTTON | |
| 10. | MAIN RELAY COIL | |
| 11. | MAIN RELAY | |
| 12. | HIGH VOLTAGE TRANSFORMER | |
| 13. | MILLIAMMETER | |
| 14. | TIMER CONNECTION LINK | |
| 15. | TRIPPING ADJUSTMENT POT | |
| 16. | TRIPPING C, Tr. | |
| 17. | TRIPPING SELECTOR SWITCH | |
| 18. | TRIPPING INDICATOR | |
| 19. | EARTH TEST PROD BLACK | |
| 20. | H.T.TEST PROD RED | |
| 21. | D'STAT ZERO MICRO SWITCH | |
| 22. | RECTIFIER | |
| 23. | TRIPPING RELAY | |
| 24. | BLEEDER RESISITANCE | |
| DIMENSIONAL DRAWING : | ||
![]() |
||