| FEATURES |
| |
Simple, rugged construction. |
| |
Coils made from high
grade CRGO Silicon Steel & 99.9% pure copper. |
| |
Output voltage variation
is smooth, continuous, breakless & linearly proportional to angular rotation. |
| |
High efficiency. |
| |
Negligible waveform
& power factor distortion. |
| |
Excellent short time
overload capacity. |
| |
Remote operation possible
by motorization. |
| |
Wide range of current
ratings. |
| |
High quality carbon
brush used for current collection. |
| ELECTRICAL
SPECIFICATIONS |
| |
MODEL |
a) Flush
Open Manual (Air Cooled) — F |
| |
|
b) Portable
Enclosed Manual (Air Cooled) — P |
| |
|
c)
In Tank Manual (Oil Cooled) — T
'F', 'P', T suffixed by 'M' means motor operated models. |
| |
|
| |
OPERATING
VOLTAGE |
For Single
Phase - 240V AC, 50-60 Hz. 1- ph. |
| |
|
For Three
Phase - 415V AC, 50 -60 Hz., 3 - ph - 4wire. |
| |
CURRENT
RATINGS |
For Oil
Cooled models, maximum current & continuouscurrent are one & the same. |
| |
|
For Air
Cooled models, the ratings are as shown below. |
| |
Maximum
Current |
0.7 |
2 |
4 |
8 |
10 |
15 |
20 |
28 |
| |
Continuous
Current |
0.6 |
1.8
|
3.8 |
6.5 |
9 |
11.5 |
16 |
22 |
| |
OPERATING
TEMP. |
0° - 45°C. |
| |
INSULATION
RESISTANCE |
Not less
than 5 Mohms at 500V DC. |
| |
DIELECTRIC
TEST |
2.5kV RMS
for 1 minute. |
| |
STORAGE
TEMP. |
-9°C to
70°C |
| |
HUMIDITY |
Upto 95%
RH |
| |
CONFORMS
TO |
I.S. 5142. |
| APPLICATIONS |
| |
Auditorium, Hotels,
Conference Halls, Exhibitions, Laboratories etc., |
| |
AC Voltage Stabilizers,
Rectifiers, Battery Chargers. |
| |
Temperature control
of Ovens, Furnaces. |
| |
Testing of Instruments,
Relays, Circuit Breakers etc. |
| |
Welding, Electro-plating,
Anodizing etc. |
| |
Colleges & Universities. |
| Ordering
Information (as per code specified below) |
| 1st
block |
Output current
rating amps |
0.7,2,4,8,10,15,20,28,40,50,60,75,100,125,150,
200,300,400, 500,600,800,1000,1200,1500 A. |
| 2nd block |
Dimmerstat (D) |
Continuously variable
voltage auto transformer. |
| 3rd block |
No. of coils |
1, 2, 3, 4, 6, 9, 12,
15. |
| 4th block |
Type of construction.
|
F, P, T
F = Flush, back of panel open.
P = Portable, floor, table mounting, air cooled with enclosure.
T = In tank, immersed in oil. |
| 5th block |
Provided with
motor drive (M) |
"Step-syn"
230V 1Ph AC 50Hz. 60 rpm motor having instantaneous start-stop-reverse characteristics. |
| 6th block |
Approx. time in secs.
for full rotation sweep time |
8,15,30,45,60,120
|