Built in Transducer Type Wattmeters & Varmeters
DESCRIPTION

'AE' Built in Transducer type Watt / Var meter is equipped with a measuring transducer & a moving coil movement. It measures Active & Reactive power in single phase, three phase - three wire or four wire systems.


FEATURES
Built in transducer.
Panel wiring is reduced.
Economy.

ELECTRICAL SPECIFICATIONS
TYPE Active, Reactive and Apparent Power.
1) 1-Phase 2) 3-Phase-3Wire 3) 3-Phase4-Wire
OPERATING VOLTAGE 110V / 240V / 415V / 440V.
OPERATING CURRENT 1A / 5A
MEASURING UNIT Active Power W, kW or MW.
 Reactive Power Var, kVar or MVar.
FREQUENCY 50Hz or 60Hz.
ACCURACY 1.5% of f.s.d.
VA BURDEN Voltage / Phase 3VA Current / Phase 1 VA
INSULATION RESISTANCE Greater than 20 Mohms at 500V DC
DIELECTRIC TEST 2kV AC for 1 minute.
OPERATING TEMP. 0°C to 55°C
STORAGE TEMP. -20°C to 70°C
HUMIDITY up to 95 % RH
INDICATION Analogue, Linear
CONFORMS TO I.S. 1248 / I.E.C.60051 (Part-3)

MECHANICAL SPECIFICATIONS
MODEL BIWV SQ 96 BIWV SQ 144
SIZE (mm) 96 x 96 x 110 144 x 144 x 110
PANEL CUTOUT (mm) 92 x 92 +0.8 138 x 138+1.0
WEIGHT (gms)(Appro.) 600 700

Ordering information
1) Type 2) Size 3) Model 4) Active or Reactive Power 5) Current with CTR if applicable
6) Voltage with PTR if applicable 7) Full scale indication.
Home